FumeGuard™ Construction
Download Declaration of Performance (318B)Download Declaration of Performance (6241B, 6242B, 6243B)
6181B, 6241B, 6242B and 6243B Insulated and Sheathed Cables
FumeGuard™ cables are rated to a maximum sustained conductor operating temperature of 90°C. This giving FumeGuard™ cables a better current rating capacity, Table 4E2A of BS7671 Wiring Regulations, and hence provides the opportunity for using a reduced conductor size when compared to 70°C rated low smoke zero halogen or low smoke fume cable equivalents.
Used for surface wiring in power and lighting applications. Sheath has UV Protection against direct sunlight.
BASEC Approved to BS7211
Conductor Area mm² |
Conductor Construction |
Mean overall Diameter mm | Conductor Resistance ohms/KM @ 20°C |
||
6181B | 6242B | 6243B | |||
1.0 | 1/1.3 | 4.10 | 4.10 x 8.65 | 4.60 x 9.70 | 18.10 |
1.5 | 1/1.37 | 4.45 | 4.55 x 8.80 | 4.75 x 11.45 | 12.10 |
2.5 | 1/1.77 | 5.05 | 5.40 x 10.50 | 5.46 x 13.40 | 7.41 |
4.0 | 7/0.85 | 6.05 | 6.10 x 12.00 | - | 4.61 |
6.0 | 7/1.04 | 6.60 | 6.90 x 13.80 | - | 3.08 |
10.0 | 7/1.35 | 7.90 | 8.40 x 18.50 | - | 1.83 |
16.0 | 7/1/70 | 9.10 | - | - | 0.727 |
Operating Temperature: |
90°C |
Colours: | White as standard. Other colours available on request. |
Cores: | 2 core, Blue and Brown, 3 core Brown, Black and Grey. |
Packaging: | 50 and 100 metres. Other lengths available on request. |
6491B, HO5Z-R, HO7Z-R, U, Single Core Insulated Cables
General-purpose power and lighting cables often used within protective conduit or trunking installations. Can also be used within light fittings, appliance wiring and control gear.
BASEC Approved to BS7211
Conductor Area mm² | Conductor Construction | Mean Overall Diameter mm | Conductor Resistance ohms @ 20°C |
1.0 | 1/1.13 | 2.35 | 18.10 |
1.5 x 7 | 7/0.53 | 3.00 | 12.10 |
2.5 x7 | 7/0.67 | 3.60 | 7.41 |
4.0 | 7/0.85 | 4.10 | 4.61 |
6.0 | 7/1.04 | 4.70 | 3.08 |
10.0 | 7/1.35 | 6.0 | 1.83 |
16.0 | 7/1.70 | 7.00 | 1.50 |
25.0 | - | - | - |
Operating Temperature: |
90°C |
Colours: | Blue, Brown, Green-Yellow. Other colours available on request. |
Cores: | Single. |
Packaging: | 50 and 100 meters. Other lengths available on request |
Technical Data
Insulation Resistance K value 90°C: | 0.037 M ohms/km |
Tensile Strength (min): | 10.0 N/mm² |
% Elongation (min): | 125% |
Hot Set Elongation at 200°C (max): | 100% |
Low Temperature Bend: | -15°C |
Voltage Test at 20°C: | Pass 2.5 KV |
Test Under Fire Conditions: | BS EN 60332 |
Corrosive Acid Gas Emissions: | <0.5% to BS EN 50267 |
Smoke Emissions: | Pass BS7211 |
2491B, HO5Z-K, Single core insulated wiresM
Flexible single core wires used typically in control panels.
Conductor Area mm² | Conductor Construction | Mean Overall Diameter mm | Conductor Resistance ohms @ 20°C |
0.5 | 16/0.20 | 2.12 | 39.00 |
0.75 | 24/0.20 | 2.33 | 26.00 |
1.0 | 32/0.20 | 2.48 | 19.50 |
1.5 | 30/0.25 | 2.98 | 13.30 |
2.5 | 50/0.25 | 3.63 | 7.98 |
4.0 | 56/0.25 | 4.23 | 4.95 |
6.0 | 84/0.30 | 4.83 | 3.30 |
10.0 | 80/0.40 | 5.85 | 1.91 |
Operating Temperature: |
90°C |
Colours: | Blue, Brown, Black, Grey, Green/Yellow. Other colours available on request. |
Cores: | Single. |
Packaging: | 50 and 100 metres. Other lengths available on request |
Technical Data
Insulation Resistance K value 90o/c: | 0.037 M ohms/km |
Tensile Strength (min): | 10.0 N/mm² |
% Elongation (min): | 125% |
Hot Set Elongation at 200o/c (max): | 100% |
Low Temperature Bend: | -15°C |
Voltage Test at 20°C: | Pass 2.5 KV |
Test Under Fire Conditions: | BS EN 60332 |
Corrosive Acid Gas Emissions: | <0.5% to BS EN 50267 |
Smoke Emissions: | Pass BS7211 |
3183B – 3185B, H05Z1Z1-F, Insulated & Sheathed Flexible Cords
Used as supply leads for domestic and office appliances and within light fittings. This cable is manufactured to HDZ1.14S1 and generally to BS650 table 27.
Range partly approved by BASEC.
Conductor Area mm² |
Conductor Construction |
Mean overall Diameter mm | Conductor Resistance ohms/KM @ 20°C |
|||
3182B | 3183B | 3184B | 3185B | |||
0.75 | 24/0.20 | 6.50 | 6.70 | 7.60 | 8.60 | 26.00 |
1.0 | 32/0.20 | 6.80 | 7.05 | 8.15 | 9.40 | 19.50 |
1.25 | 40/0.20 | 7.50 | 8.05 | - | - | 15.60 |
1.5 | 30/0.25 | 7.80 | 8.25 | 9.60 | 10.60 | 13.30 |
2.5 | 50/0.25 | 9.25 | 10.20 | 11.30 | - | 7.98 |
4.0 | 56/0.3 | - | 11.5 | 12.5 | - | 4.95 |
Operating Temperature: |
70°C (90°C available on request) |
Colours: | White and Black sheath. Other colours available on request |
Packaging: | 50 and 100 metres. Other lengths available on request |
These cables are intended for the same application as PVC cables but where a Low Smoke Halogen requirement is needed. |
Insulation: Made with Low Smoke Zero Halogen Thermoplastic Material (TI6)
Conductor Resistance: | As per BSEN60228 |
Insulation Thickness: | As per HD21.14 S1 |
Insulation Resistance (min): | 0.02 M ohms/Km at 70°C |
Tensile Strength (min): | 7.5 N/mm² |
% Elongation (min): | 150% |
Hot Set Elongation (max): | 100% at 200°C |
Flame Test: | BS EN 60332 |
Smoke Emission: | As per BS EN 61034 |
Corrosive Acid Gas Emissions: | <0.5% to BS EN 50267 |
Voltage Test: | Pass at 2.5KV 20°C |
Sheating: Made with Low Smoke Zero Halogen Thermoset Material (TM7)
Sheath Thickness: | As per HD 21.14 S1 |
Cable OD: | As per HD 21.14 S1 |
Tensile Strength (min): | 7.5 N/mm² |
% Elongation (min): | 150% |
Voltage Test: | Pass 2.5 Kv |
Oxygen Index: | 35% at 270°C |
Corrosive Acid Gas Emissions: | < 0.5% to BS EN 50267 |
Test Under Fire Conditions: | BS EN 60332 |