FumeGuard™ 6181B, 6241B, 6242B and 6243B Insulated and Sheathed Cables
Download Declaration of Performance (6181B, 6192B, 6193B)Download Declaration of Performance (6241B, 6242B, 6243B)
6181B, 6241B, 6242B and 6243B Insulated and Sheathed Cables
FumeGuard™ cables are rated to a maximum sustained conductor operating temperature of 90°C. This giving FumeGuard™ cables a better current rating capacity, Table 4E2A of BS7671 Wiring Regulations, and hence provides the opportunity for using a reduced conductor size when compared to 70°C rated low smoke zero halogen or low smoke fume cable equivalents.
Used for surface wiring in power and lighting applications. Sheath has UV Protection against direct sunlight.
BASEC Approved to BS7211
Conductor Area mm² |
Conductor Construction |
Mean overall Diameter mm | Conductor Resistance ohms/KM @ 20°C |
||
6181B | 6242B | 6243B | |||
1.0 | 1/1.3 | 4.10 | 4.10 x 8.65 | 4.60 x 9.70 | 18.10 |
1.5 | 1/1.37 | 4.45 | 4.55 x 8.80 | 4.75 x 11.45 | 12.10 |
2.5 | 1/1.77 | 5.05 | 5.40 x 10.50 | 5.46 x 13.40 | 7.41 |
4.0 | 7/0.85 | 6.05 | 6.10 x 12.00 | - | 4.61 |
6.0 | 7/1.04 | 6.60 | 6.90 x 13.80 | - | 3.08 |
10.0 | 7/1.35 | 7.90 | 8.40 x 18.50 | - | 1.83 |
16.0 | 7/1/70 | 9.10 | - | - | 0.727 |
Operating Temperature: |
90°C |
Colours: | White as standard. Other colours available on request. |
Cores: | 2 core, Blue and Brown, 3 core Brown, Black and Grey. |
Packaging: | 50 and 100 metres. Other lengths available on request. |