Used as supply leads for domestic and office appliances and within light fittings. This cable is manufactured to HDZ1.14S1 and generally to BS650 table 27.
FumeGuard Insulated & Sheathed Flexible Cords |
FumeGuard LSHF Flexible Cable 31838
Range partly approved by BASEC.
Conductor Area mm² | Conductor Construction | Mean overall Diameter mm | Conductor Resistance ohms/KM @ 20°C |
|||
3182B | 3183B | 3184B | 3185B | |||
0.75 | 24/0.20 | 6.50 | 6.70 | 7.60 | 8.60 | 26.00 |
1.0 | 32/0.20 | 6.80 | 7.05 | 8.15 | 9.40 | 19.50 |
1.25 | 40/0.20 | 7.50 | 8.05 | - | - | 15.60 |
1.5 | 30/0.25 | 7.80 | 8.25 | 9.60 | 10.60 | 13.30 |
2.5 | 50/0.25 | 9.25 | 10.20 | 11.30 | - | 7.98 |
4.0 | 56/0.3 | - | 11.5 | 12.5 | - | 4.95 |
Attributes
Operating Temperature: | 70°C (90°C available on request) |
Colours: | White and Black sheath. Other colours available on request |
Packaging: | 50 and 100 metres. Other lengths available on request |
These cables are intended for the same application as PVC cables but where a Low Smoke Halogen requirement is needed.
Insulation
Made with Low Smoke Zero Halogen Thermoplastic Material (TI6)
Conductor Resistance: | As per BSEN60228 |
Insulation Thickness: | As per HD21.14 S1 |
Insulation Resistance (min): | 0.02 M ohms/Km at 70°C |
Tensile Strength (min): | 7.5 N/mm² |
% Elongation (min): | 150% |
Hot Set Elongation (max): | 100% at 200°C |
Flame Test: | BS EN 60332 |
Smoke Emission: | As per BS EN 61034 |
Corrosive Acid Gas Emissions: | <0.5% to BS EN 50267 |
Voltage Test: | Pass at 2.5KV 20°C |
Sheating
Made with Low Smoke Zero Halogen Thermoset Material (TM7)
Sheath Thickness: | As per HD 21.14 S1 |
Cable OD: | As per HD 21.14 S1 |
Tensile Strength (min): | 7.5 N/mm² |
% Elongation (min): | 150% |
Voltage Test: | Pass 2.5 Kv |
Oxygen Index: | 35% at 270°C |
Corrosive Acid Gas Emissions: | < 0.5% to BS EN 50267 |
Test Under Fire Conditions: | BS EN 60332 |