Fumeguard Single Core Insulated Cables

General-purpose power and lighting cables often used within protective conduit or trunking installations. Can also be used within light fittings, appliance wiring and control gear.

Specification

6491B, HO5Z-R, HO7Z-R, U, Single Core Insulated Cables

Conductor Area mm²Conductor ConstructionMean Overall Diameter mmConductor Resistance ohms @ 20°C
1.01/1.132.3518.10
1.5 x 77/0.533.0012.10
2.5 x77/0.673.607.41
4.07/0.854.104.61
6.07/1.044.703.08
10.07/1.356.01.83
16.07/1.707.001.50
25.0---

Attributes

Operating Temperature:90°C
Colours:Blue, Brown, Green-Yellow. Other colours available on request.
Cores:Single.
Packaging:50 and 100 meters. Other lengths available on request

Statistics

Insulation Resistance K value 90°C:0.037 M ohms/km
Tensile Strength (min):10.0 N/mm²
% Elongation (min):125%
Hot Set Elongation at 200°C (max):100%
Low Temperature Bend:-15°C
Voltage Test at 20°C:Pass 2.5 KV
Test Under Fire Conditions:BS EN 60332
Corrosive Acid Gas Emissions:<0.5% to BS EN 50267
Smoke Emissions:Pass BS7211